cooling load sizingCooling Load Sizing

To size your production machine cooling load use the following information: Calculate the total lbs/hour of material your machine uses and divide it by the lbs/ton listed below for your specific process. This will give you the tons of cooling required at 50° F leaving water temperature.

When operating below 50° F you must decrease the rated chiller cooling capacity by 2% for every one degree F you operate below 50° F.

To correct for 45° F operation you would divide the chiller rated cooling load by 0.9. See calculation: 100% - (2% x 5° F below 50° F) = 90% or 0.9.

 

INJECTION MOLDING = 1 LBS/TON

EXTRUSION = 1 LBS/TON

 

 

30 lbs/hour HDPE
35 lbs/hour LDPE
35 lbs/hour Acrylic
35 lbs/hour PP
40 lbs/hour Nylon
40 lbs/hour Derlin
40 lbs/hour Urethane
45 lbs/hour PET
50 lbs/hour PS
50 lbs/hour ABS
50 lbs/hour PC
50 lbs/hour Acetal
70 lbs/hour PVC

SHEET CALENDERING

35 lbs/hour PE
60 lbs/hour ABS
60 lbs/hour PS

PROFILE

50 - 60 lbs/hour HDPE
50 - 60 lbs/hour LDPE
50 - 60 lbs/hour PP
50 - 60 lbs/hour PET
60 - 75 lbs/hour ABS
60 - 75 lbs/hour PVC

 

 

FEED THROAT:

1/2 ton up to 400 ton injection.
1 ton over 400 ton injection.

Barrel = 1 ton/" screw dia
Screw = 2 tons
Throat = 1/2 ton up to 3"
Throat = 1 ton 4" to 6"
Gear drive = 100 hp/ton
(oil cooling)

 

 

BLOW HOLDING = 1 TON

VACUUM FORMING = 1 TON

 

 

40 lbs/hour HDPE
40 lbs/hour PET
40 lbs/hour PVC

70 lbs/hour HDPE & LDPE
70 lbs/hour PP
200 lbs/hour PS
250 lbs/hour PVC

 

 

HOT RUNNER MOLDS convert heater watts to btu's and divide by 2. (watts x 3.414 divide by 24,000 Btu's)

MOTOR COOLING LOAD FOR PORTABLE CHILLERS

 

 

Hydraulic cooling:

8 hp = 1 ton

Vacuum pumps:

8 hp = 1 ton

Air compressors:

8 hp = 1 ton (internal oil cooling).

 

8 hp = 1 ton (after cooler cooling).

Chilled water flow rate is 2.4 gpm/ton.

 

Chiller ton is 12,000 Btu's

 

Chiller operating temperature range with water is from 45° F. to 60° F. leaving water temperature.

Chiller operating temperature range with glycol/water is from 25 F. to 45° F. leaving water temperature.

-
Whaley Products, Incorporated
526 Charlotte Avenue, Burkburnett, TX 76354
Phone: 940-569-4116 ~ Email: sales@waterchillersystems.com

Copyright © 2007 | Whaley Products, Inc. | All rights reserved

WPI Water Cooling Site Links
air-cooled modular cooling
air-cooled rack cooling
air-cooled stationary cooling
air handlers
beverage cooling
centrifugal cooling
central chillers
central chiller stations
cooling liquid bath
cooling tower pumps
compressors
custom chiller design
fractional chillers
glycol cooling chillers
glycol/water cooling
heat transfer
heat exchangers
helical rotary cooling
reciprocation chillers
rotary screw cooling
scroll liquid cooling
specialty chillers
multi-circuit cooling
portable water chillers
pump and tank cooling
pump and tank stations
pumps and tanks
process chilling
process cooling
refrigeration cooling systems
small chillers
tanks
temperature control
water cooling