940.569.4116

Open Loop Cooling Tower

Cooling Tower Systems
Capacity Range: 10 to 500 Ton
Classification: Open-Loop

Standard Features

  • Induced draft counter flow design
  • Fabricated from fiberglass reinforced polyester (FRP)
  • ABS nozzle(s) used to prevent clogging and allow even spray across the fill
  • Side or bottom outlet available
  • Louvers installed to prevent debris in the air from entering tower water
  • All fill, drift, and louvers are manufactured completely out of 136 PVC
  • Top mount direct drive fans
  • Rust resistant
  • FRP shell constructed with a UV protectant
  • Tower is constructed of lightweight components
  • Steel frames available for all sizes with 4” C-Channel and 2-Part Epoxy paint to prevent rusting
  • Water make-up valves
  • Bottom or side outlets
  • Inlets available on 2 sides of cooling tower
  • Internal FRP cooling tower basin
  • Balancing line connections for multi-cell application

10 to 25 Ton Specifications (1-Phase & 3-Phase)

Open Loop Cooling Towers - 10 Ton to 25 Ton
Model Tower Tons / KW BTU/hr Flow Rate Dimensions
L x W x H
Tower Basin Volume Unit Weight
( lbs )
Fan Motor HP / RPM Nominal Air Flow Fan Motor FLA 208-240/1 Fan Motor FLA 208-240/3 Fan Motor FLA 440-460/3 Fan Motor FLA 575/3 Fan Motor FLA 380-415/3
WP650-10 10 Ton/44KW 150,000 30 GPM 24"L x 24"W x 78"H 25 gal 300 lbs 1/2HP - 1725RPM 3,000 CFM 5.4 2.2 1.0 0.8 1.2
WP650-15 15 Ton/66KW 225,000 45 GPM 24"L x 24"W x 78"H 25 gal 300 lbs 1/2HP - 1725RPM 3,250 CFM 5.4 2.2 1.0 0.8 1.2
WP850-20 20 Ton/88KW 300,000 60 GPM 32"L x 32"W x 84"H 44 gal 400 lbs 3/4HP - 1140RPM 6,000 CFM 8.8 3.1 1.4 1.1 2.2
WP850-25 25 Ton/110KW 375,000 75 GPM 32"L x 32"W x 84"H 44 gal 400 lbs 3/4HP - 1140RPM 6,500 CFM 8.8 3.1 1.4 1.1 2.2

*Standard Site Conditions:  85°F/29.4°C Leaving Water Temperature,  95°F/35°C Dry Bulb (Ambient) Temperature,  78°F/25.6°C Wet Bulb Temperature*

30 to 125 Ton Specifications (1-Phase & 3-Phase)

Open Loop Cooling Towers - 30 Ton to 125 Ton
Model Tower Tons / KW BTU/hr Flow Rate Dimensions
L x W x H
Tower Basin Volume Unit Weight
( lbs )
Fan Motor HP / RPM Nominal Air Flow Fan Motor FLA 208-240/1 Fan Motor FLA 208-240/3 Fan Motor FLA 440-460/3 Fan Motor FLA 575/3 Fan Motor FLA 380-415/3
WP1250-30 30 Ton/132KW 450,000 90 GPM 48"L x 48"W x 102"H 100 gal 630 lbs 2HP - 1140RPM 11,300 CFM 13.2 7.5 3.4 2.7 4.1
WP1250-40 40 Ton/176KW 600,000 120 GPM 48"L x 48"W x 102"H 100 gal 630 lbs 2HP - 1140RPM 12,000 CFM 13.2 7.5 3.4 2.7 4.1
WP1550-50 50 Ton/220KW 750,000 150 GPM 60"L x 60"W x 113"H 150 gal 911 lbs 3HP - 1155RPM 15,000 CFM 18.7 10.7 4.8 3.9 5.8
WP1550-75 75 Ton/330KW 1,125,000 225 GPM 60"L x 60"W x 113"H 150 gal 911 lbs 3HP - 1155RPM 17,500 CFM 18.7 10.7 4.8 3.9 5.8
WP1850-100 100 Ton/440KW 1,500,000 300 GPM 72"L x 72"W x 122"H 224 gal 1186 lbs 5HP - 1150RPM 20,500 CFM 30.8 16.7 7.6 6.1 9.2
WP1850-125 125 Ton/550KW 1,875,000 375 GPM 72"L x 72"W x 122"H 224 gal 1186 lbs 5HP - 1150RPM 22,700 CFM 30.8 16.7 7.6 6.1 9.2

*Standard Site Conditions:  85°F/29.4°C Leaving Water Temperature,  95°F/35°C Dry Bulb (Ambient) Temperature,  78°F/25.6°C Wet Bulb Temperature*

150 to 500 Ton Specifications (1-Phase & 3-Phase)

Multiple Cell Open Loop Cooling Towers - 150 Ton to 500 Ton
Model Tower Tons / KW BTU/hr Flow Rate Dimensions
L x W x H
Tower Basin Volume Unit Weight
( lbs )
Fan Motor HP / RPM Nominal Air Flow Fan Motor FLA 208-240/1 Fan Motor FLA 208-240/3 Fan Motor FLA 440-460/3 Fan Motor FLA 575/3 Fan Motor FLA 380-415/3
WP2-1550-150 150 Ton/660KW 2,250,000 450 GPM 2each 60"L x 60"W x 113"H 2each 150 gal 2x911lbs 2ea. 3HP - 1155RPM 35,000 CFM 37.4 21.4 9.6 7.8 11.6
WP2-1850-200 200 Ton/880KW 3,000,000 600 GPM 2each 72"L x 72"W x 122"H 2each 224 gal 2x1186lbs 2ea. 5HP - 1150RPM 41,000 CFM 61.6 33.4 15.2 12.2 18.4
WP2-1850-250 250 Ton/1100KW 3,750,000 750 GPM 2each 72"L x 72"W x 122"H 2each 224 gal 2x1186lbs 2ea. 5HP - 1150RPM 45,400 CFM 61.6 33.4 15.2 12.2 18.4
WP3-1850-300 300 Ton/1320KW 4,500,000 900 GPM 3each 72"L x 72"W x 122"H 3each 224 gal 3x1186lbs 3ea. 5HP - 1150RPM 61,500 CFM 92.4 50.1 22.8 18.3 27.6
WP3-1850-375 375 Ton/1650KW 5,625,000 1125 GPM 3each 72"L x 72"W x 122"H 3each 224 gal 3x1186lbs 3ea. 5HP - 1150RPM 68,100 CFM 92.4 50.1 22.8 18.3 27.6
WP4-1850-400 400 Ton/1760KW 6,000,000 1200 GPM 4each 72"L x 72"W x 122"H 4each 224 gal 4x1186lbs 4ea. 5HP - 1150RPM 82,000 CFM 123.2 66.8 30.4 24.4 34.8
WP4-1850-500 500 Ton/2200KW 7,500,000 1500 GPM 4each 72"L x 72"W x 122"H 4each 224 gal 4x1186lbs 4ea. 5HP - 1150RPM 90,800 CFM 123.2 66.8 30.4 24.4 34.8

*Standard Site Conditions:  85°F/29.4°C Leaving Water Temperature,  95°F/35°C Dry Bulb (Ambient) Temperature,  78°F/25.6°C Wet Bulb Temperature*

Request a Quote